Refrigerant log report

The refrigerant log report lists every refrigerant charge, top-up and recovery recorded in Thermal for US equipment, with each unit's annualized leak rate checked against the federal threshold for its appliance class. It is a recordkeeping tool: it keeps the records the rules ask for, and it does not decide whether you are in compliance.

Report library14 columnsRelated: 5 linksSee it live in Thermal
01

The columns.

One row per refrigerant transaction, with the unit's leak rate and the threshold that applies to it.

  • ForService managers and the person who keeps refrigerant records for US equipment.
  • AnswersWhat refrigerant was added to or recovered from each unit, by whom, and which units are leaking faster than the threshold that applies to them.
  • StatusAvailable in Thermal today: Reports, Refrigerant log. It is a recordkeeping tool; it does not certify compliance.
  • Date, customer, site, equipment and serialWhere and on which unit the transaction happened.
  • Transaction, refrigerant and quantityCharge, top-up or recovery, the refrigerant, and the amount in ounces.
  • Leak rate and thresholdAnnualized leak rate, the threshold for the unit's class, and a flag when it is over.
  • ExemptUnits below the size the federal rules apply to, labelled with the reason.
  • CY additionRefrigerant added to the unit this calendar year, for the 125%-of-full-charge reporting trigger.
  • Technician and EPA cert #Who did the work and the EPA Section 608 certificate number recorded for them.
  • JurisdictionUS federal rules: EPA Section 608 leak repair for ozone-depleting refrigerants and 40 CFR 84.106 for HFCs from January 1, 2026, plus California's own leak rules. Canadian and other jurisdictions are not covered.
  • SourceRefrigerant transactions recorded on equipment and jobs, each unit's full charge, appliance class and refrigerant, and technician credentials.
  • UpdatesWhen the page loads, for the date range, customer and site you choose. A leak-rate check also runs whenever a transaction is saved.
  • In the appapp.trythermal.com/reports/refrigerant-compliance
  • Next stepStart free, then open Reports, then Refrigerant log. Already on Thermal? Open the report. To see it on sample data first, book a demo.
02

How the report works.

What the rules say, and what Thermal does

Under EPA's Section 608 rules, appliances holding 50 pounds or more of ozone-depleting refrigerant must have leaks repaired once the leak rate passes 20% for commercial refrigeration, 30% for industrial process refrigeration or 10% for comfort cooling. From January 1, 2026, 40 CFR 84.106 applies the same rates to appliances with 15 pounds or more of HFC refrigerant (excluding residential and light commercial air conditioning), and owners of appliances that leak 125% or more of their full charge in a calendar year must report to EPA by March 1 of the following year. Sources: EPA's Section 608 leak repair page and the eCFR text of 40 CFR 84.106, read on November 8, 2026.

Thermal applies those thresholds to the transactions you record, flags units over them, and keeps the technician's certificate number on each row. Whether a repair, report or retrofit plan is required, and whether it was done in time, is a decision for the owner or operator and their advisers. Rules change: check the official text before relying on any threshold.

A worked example

Illustrative figures, not customer data. A supermarket's commercial refrigeration rack holds 120 pounds of R-404A. A technician adds 28 pounds a year after the last addition and records it against the unit. The annualized leak rate is about 28 ÷ 120, or 23%, over the 20% commercial refrigeration threshold, so the row is flagged and an alert is raised.

The service manager schedules the leak search and repair, and the follow-up verification visit is recorded on the same unit, so the history the owner may need is in one place.

How Thermal builds the log

Each refrigerant transaction is recorded against a piece of equipment on a job, with the refrigerant, quantity and technician. Thermal combines it with the unit's full charge and appliance class to calculate the leak rate and pick the threshold, and checks the leak rate again each time a transaction is saved.

03

Questions about this report.

Does Thermal make my company compliant?

No. Thermal keeps refrigerant records and flags units over a threshold. Whether you are in compliance is decided under the regulations by the owner or operator and their advisers, not by the software.

Which jurisdictions does the report cover?

US federal rules under EPA Section 608 and 40 CFR Part 84, and California's leak rules. It does not apply Canadian federal or provincial rules or other states' rules.

Which units are exempt?

Units below the size the rules apply to are labelled exempt: under 50 pounds for ozone-depleting refrigerants under Section 608, and under 15 pounds for HFCs under Part 84.

Is the technician's certification recorded?

Yes. Each row carries the EPA Section 608 certificate number recorded for the technician who did the work, taken from their credentials in Thermal.

05

These reports, on your own data.

If you want to see how they read on your branch's actual work orders and billing, that's a demo.